The Leak Detection Panel (LDP) has a leak-detected, a sensor healthy, and a sensor fault LED per zone. In the event of a leak, the alarm LED will flash red, the buzzer will sound, the valve will operate (if connected) & the relays will energize. Pressing the mute button will silence the buzzer. The Leak LED will remain illuminated until the sensor has been dried. In the event of a sensor fault, the sensor fault LED will change from green to red, buzzer will sound and the fault relay energize. The mute button can be pressed to silence the buzzer. The fault LED will remain red until the sensor fault has been repaired. The panel will self-reset in both instances unless the alarm reset link is set to latch. The LDP test button can be pressed to test the functionality of all LED’s.
You can either buy our panels on their own or as a part of a kit for all your leak detection needs
Compatible Sensors
Cable Sensor
Probe Sensor
Mini Probe Senor
Mini Pad Sensor
Over Flow Sensor
Over-Temperature